Direct Replacement Upgrades | ||||||||||||||||||||||||||||||||||||||
No wiring changes necessary (see notes). Use existing wiring base and flame scanner. |
||||||||||||||||||||||||||||||||||||||
| ||||||||||||||||||||||||||||||||||||||
Notes: L1-13, 13-3 circuits: Some C-Series and D-Series controls were installed on a burner that did not have a fuel valve end switch terminal (13 – 3) and the operating control was wired between L1 and 3. When upgrading to a Flame-Monitor on these installations, after verifying a fuel valve end switch is not installed (e.g., no wire on terminal 13), jumper terminal 13 to 3. |
||||||||||||||||||||||||||||||||||||||
Early Spark Termination (Terminal X): On the non-modulating C-Series and D-Series (70D30) controls, terminal X would provide a 5 second pilot trial for ignition (PTFI). If terminal X is required, terminal 5 must be jumpered to terminal 10 when using the EP380, EP381, or EP390 programmers. | ||||||||||||||||||||||||||||||||||||||
CAUTION: Refer to Bulletin E-1101 for proper installation, grounding, operational and safety checkout procedures. Perform safety checks of the entire system prior to allowing fuel entry to boiler. | ||||||||||||||||||||||||||||||||||||||
|
||||||||||||||||||||||||||||||||||||||
* Ensure S2 is connected to earth ground when using ERT1 Fireye Primeline Products. | ||||||||||||||||||||||||||||||||||||||